• Voltage Input Signal (1-5V)
    Current value in (V)
    Measurement Output Parameters
    Unit (bar,psi,mmH2O,mA,Volt,etc.)
    Low Limit (LRV)
    High Limit (URV)
    Output value
    Sorry, a graphic could not be displayed here, because your browser does not support HTML5 Canvas.

    Formula

    This tool uses the following formula to calculate the measurement reading from a voltage signal input over a 1-5V range:

    Measurement Rdg = (High Limit  - Low Limit) x (V out -1) / 4 + Low Limit

    Current Value in Volts (1-5V) Reading

    Add the analogue input signal which is 1 - 5 Volts

    Measurement Unit

    Enter the measurement unit associated with the output values,in this case has been chosen Bar

    Lowest Measurement

    Add the minimum possible value for the measurement range of your instrument, Normally should be zero but you can also add negative (-) or positive (+) values as well.

    Highest Measurement

    Add the maximum possible value for the measurement range of your instrument, which normally should be maximum Range (URV) but you can also add negative (-) or positive (+) values as well.
     

    Output Value - Answer

    This is the ideal converted measurement for your instrument